Troubleshooting Communication Problems with Pentair Equipment

Communication issues are among the most common problems people run into with their Pentair pool equipment.  The following problems can be caused by faulty communication: pressing a button on a remote or indoor controller does nothing  an Intelliflo pump won't run the schedule screenlogic can't control the system communication timeout errors show on the intellitouch indoor panel an Easytouch wireless remote or indoor panel shows "No Comm" The good news is finding the cause of these problems isn't rocket science and involves no black magic. The first thing you need to know is that Pentair systems use an RS-485 interface for serial communication between connected devices, operating at 9600 baud (8/N/1).  If you're familiar with the RS-485 standard you can skip the next section, otherwise I'd recommend giving it a quick read to get the gist... RS-485 Basics Unlike serial interfaces that have separate Transmit (TX) and Receive (RX) wires, RS-485